New
Technology InteliGen EE is a controller for both single and
multiple gen-sets operating in standby or parallel modes,
where an Engine with ECU is used. Compact construction is
optimized for these purposes, various HW modifications allow
the customer to select the optimum type for a particular application.
Built-in synchronizer and digital isochronous load sharer
allow total integrated solution for gen-sets in standby, island
parallel or mains parallel. Native cooperation of up to 32
gen-sets is a standard feature.
InteliGenNT EE supports many standard ECU types and is especially
designed to easily integrate new ones.
Powerful graphic display with user-friendly control allows
even new users to find quickly the required information.
ComAp is open to various customized firmware solutions.
Features:
- Support
of engines with ECU (J1939, ModBus and other proprietary
interfaces); alarm codes displayed in text form
- AMF function
- Automatic
synchronizing and power control (via ECU)
- Baseload,
Import/Export
- Peak
shaving
- Voltage
and PF control (AVR)
- Generator
measurement: U, I, Hz, kW, kVAr, kVA, PF, kWh, kVAhr
- Mains
measurement: U, I, Hz, kW, kVAr, PF
- Inputs
and outputs configurable for various customer needs
- RS232/RS485
interface with ModBus protocol support; Analog/GSM/ISDN/CDMA
modem communication support;
- SMS
messages; ECU ModBus interface
- Event-based
history (up to 500 records) with customer-selectable list
of stored values; RTC; statistic values
- Integrated
PLC programmable functions
- Interface
to remote display unit (IG-Disp)
- Dimensions
180x120 mm (front panel)
- Sealed
to IP65
InteliGen
EE NT.pdf |

Benefits
- HW
optimized for cooperation with an ECU (Electronic Control
Unit)
- Excellent
configurability allows matching exactly the customer’s
needs
- Complete
integrated gen-set solution and signal sharing via CAN bus
– minimum external components needed
- Many
communication options – easy remote supervising and
servicing
Perfect price / performance ratio
- Gen-set
performance log for easy problem tracing
|